3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
ENG
31
6.4.1 Timer Beacon
Timer operation is indicated by a beacon labelled RUN:
Timer Status RUN beacon Timer Status RUN beacon
Reset Off Hold Flashing
Run On End Off
6.4.2 Logic outputs
The timer may be configured to operate an output when it is running or during the end state
Note:-
• Power up - the ‘run’ state is selected if a Soft Start or Delay timer is configured or the ‘Reset’ state is selected if a
Dwell timer is configured.
• Auto/Manual is only available when the timer is in Reset
• Ramp Rate – it is recommended that ramp rate is used only with a Dwell type timer
Quick access to the timer operating parameters is available in Level 2 by pressing
!
. Repeat pressing of this button
shows Timer Status, Dwell, Working Output, SP1, SP2, etc
6.4.3 Power Cycling
If the power is turned off when the timer is running it will come back on as follows:-
For a Dwell type timer it will come back on in Reset
For a Delayed Switch on timer or a Soft Start timer, the controller will come back on in the Run condition and start again
from the beginning.