3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
Mnemonic Scrolling Display and description Range
LD.AMP LOAD CURRENT is the measured load current when the power
demand is on
CT Range
LK.AMP LEAK CURRENT is the measured leakage current when the power
demand is off.
CT Range
LD.ALM LOAD CURRENT THRESHOLD sets a low alarm trip point for the load
current as measured by the CT. This detects partial load failure.
CT Range
LK.ALM LEAK CURRENT THRESHOLD sets a high alarm trip point for the
leakage current measured by the CT.
CT Range
HC.ALM OVERCURRENT THRESHOLD sets a high alarm trip point to show over
current as measured by the CT
CT Range
ADDR ADDRESS - communications address of the controller. 1 to 254 1 to 254
HOME
STD
Standard
OP
Output power
Tr
Time remaining
ELAP
Time elapsed
AL
First alarm
setpoint
CT
Load current
HOME DISPLAY Defines the parameter which appears in the lower
section of the HOME display
CLr
Clear (blank)