3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
ENG
25
Mnemonic Scrolling Display and description Range
TM.RES TIMER RESOLUTION selects hours or minutes (only when in Reset)
Hour
min
Hours
Minutes
THRES TIMER START THRESHOLD The timer will not run until the PV
becomes in range of the value set by this parameter. This value can
be changed when the timer is running.
OFF or 1 to 3000
OFF
Control OP goes
to zero
Dwel
Control continues
at SP1
END.T TIMER END TYPE The action of the timer when it has timed out can
be selected from Dwell (control continues at the setpoint), Off
(control outputs turn off), SP2 (control at setpoint 2). Can be changed
while the timer is running.
SP2
Go to SP2
SS.PWR SOFT START POWER LIMIT Sets the power limit during start up -100 to 100%
SS.SP SOFT START SETPOINT sets the threshold below which the power is
limited
Between SP.HI and SP.LO
DWELL SET TIME DURATION - can be adjusted while the timer is running.
This parameter only appears for a Dwell type timer.
0:00 to 99.59 hh:mm: or
mm:ss
T.REMN TIME REMAINING Time remaining to reach the set time 0:00 to 99.59 hh:mm: or
mm:ss
This section applies to Alarms only If an alarm is not configured the parameters do not appear
A1.--- - to
A4.---
ALARM 1 (2, 3 or 4) SETPOINT sets the threshold value at which an
alarm is detected. Up to four alarms are available and are only shown
if configured.
--- = the mnemonic for the alarm type which may be:-
SP.HI to SP.LO