Mnemonic Scrolling Display and description Range
HYST.H HEATING HYSTERESIS sets the difference in PV units between output
1 turning off and turning on.
Only shown if channel 1 control action is On/Off.
0.1 to 200.0 display units
HYST.C COOLING HYSTERESIS sets the difference in PV units between output
2 turning off and turning on.
Only shown if channel 2 control action is On/Off.
0.1 to 200.0 display units
D.BAND CHANNEL 2 DEADBAND adjusts a zone between heating and cooling
outputs when neither output is on.
Off = no deadband. 100 = heating and cooling off.
On/Off controllers only.
OFF or 0.1 to 100.0% of the
cooling proportional band
OP.HI OUTPUT HIGH limits the maximum heating power applied to the
process or a minimum cooling output.
+100% to OP.LO
1. (2 or 4)
PLS.
OUTPUT 1 (2 or AA) MINIMUM PULSE TIME to set the minimum
on/off time for the output. Relay outputs are adjustable from 0.1 to
150 seconds. Logic outputs set to Auto = 55ms.
Auto to 150.0
This section applies to current transformer input only. If the CT option is not configured the parameters do not
appear