5.4.1 To Set The Required Temperature.
From the HOME display:-
Press
to raise the setpoint
Press
to lower the setpoint
The new setpoint is entered when the button is released and is indicated by a brief flash of the display.
5.4.2 Alarm Indication
If an alarm occurs the red ALM beacon will flash, a scrolling message will give the source of the alarm and the alarm
(relay) output will operate.
Press
!
and
!
(ACK) together to acknowledge
If the alarm is still present the ALM beacon lights continuously.
The action which takes place depends on the type of alarm configured:-
Non latching A non latching alarm will reset itself when the alarm condition is removed
Auto
Latching
An auto latching alarm requires acknowledgement before it is reset. The acknowledgement can occur
BEFORE the condition causing the alarm is removed.
Manual
Latching
The alarm continues to be active until both the alarm condition is removed AND the alarm is
acknowledged. The acknowledgement can only occur AFTER the condition causing the alarm is
removed.