3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
Mnemonic Scrolling Display and description Range
Lo
Full Scale
Low
Bnd
Deviation
Band
dH i
Deviation
High
Hi
Full Scale
High
dLo
Deviation
Low
This section applies to control parameters
A.TUNE AUTOTUNE automatically sets the control parameters to match the
process characteristics.
Off
On
Disable
Enable
PB PROPORTIONAL BAND sets an output which is proportional to the
size of the error signal. Units may be % or display units.
1 to 9999 display units
TI INTEGRAL TIME removes steady state control offsets by ramping the
output up or down in proportion to the amplitude and duration of the
error signal.
Off to 9999 seconds
TD DERIVATIVE TIME determines how strongly the controller will react
to the rate of change in the process value. It is used to prevent
overshoot and undershoot and to restore the PV rapidly if there is a
sudden change in demand.
Off to 9999 seconds
MR MANUAL RESET applies to a PD only controller i.e. the integral term
is turned off. Set this to a value of power output (from +100% heat, to
-100% cool which removes any steady state error between SP and PV.
-100 to 100%
R2G RELATIVE COOL GAIN adjusts the cooling proportional band relative
to the heating proportional band. Particularly necessary if the rate of
heating and rate of cooling are very different. (Heat/Cool only)
0.1 to 10.0