3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
ENG
9
3.4 Input/Output 1 (Relay or Logic)
This may be a logic input or a logic output or a relay output
Relay output normally open (Form A), 2A 264Vac resistive
OR
Logic output to drive SSR (not isolated)
Logic level On/High - 12Vdc at 5 to 40mA max
Logic level Off/Low - <100mV <100µA
OR
Digital Input (contact closure)
3.5 Output 2 (Relay or Logic)
This is optional and is output only. It may be relay or logic output as output 1.
3.6 AA Output Relay
Changeover relay (Form C) rated 2A 264Vac resistive
* General Note About Relays and Inductive Loads
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves. Through
the internal contacts, these transients may introduce disturbances which could affect the performance of the instrument.
For this type of load it is recommended that a ‘snubber’ is connected across the normally open contact of the relay
switching the load. The snubber recommended consists of a 15nF series connected resistor/capacitor (typically
15nF/100). A snubber will also prolong the life of the relay contacts.
WARNING
When the relay contact is open or it is connected to a high impedance load, the snubber passes a current (typically 0.6mA
at 110Vac and 1.2mA at 240Vac). You must ensure that this current will not hold on low power electrical loads. If the
load is of this type the snubber should not be connected.