20
ENG
3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
5.4.5 To Select Manual Operation and Adjust the Output Power
Press
and hold
▼
▼▼
▼
and
▲
▲▲
▲
(Mode) together for more than 1 second. This can only be
accessed from the HOME display.
1. ‘Auto’ is shown in the upper display. The lower display will scroll the longer alternate
description of this parameter, ie ’ loop m ode – auto m anual off’
2. Press
▲
to select ‘mAn’. This is shown in the upper display and the MAN beacon is lit.
3. The controller will return to the HOME display. The upper display shows PV. The lower
display shows demand power. At the point of changeover the manual demand power is the
same as it was when in Auto (bumpless transfer auto to manual).
4. Press
▼
or
▲
to lower or raise the power. The output power is continuously updated
when these buttons are pressed
5. The loop can also be turned off (zero power output demand) by selecting ‘OFF’ in the
upper display. Loop break is also turned off. The controller will return to the HOME
display. The upper display shows the PV. The lower display shows OFF. The MAN beacon
is lit in this mode.
6. To Return to Automatic operation, press
▼
and
▲
together. Then press
▼
to select ‘Auto’. At the
point of changeover to automatic operation the power demand takes the current value and gradually changes
to that required by the controller bumpless transfer manual to auto)
t + u
t
t + u
Komentarze do niniejszej Instrukcji