3200 Series
A
CS 3216 Operators Manual 29
DESCRIPTION:
This status bit states whether this unit is currently processing.
0 = not currently processing (3200 manual mode)
1 = processing (3200 auto mode)
ALARM, SYSTEM
BIT#:
1
DESCRIPTION:
This status bit states an alarm is present. In the 3200, this is set if any of the 4 temperature alarms are set, or
if Sensor Break, Span Error, or Loop break is set.
ALARM, PROCESS
BIT#
2
DESCRIPTION:
This bit indicates that an alarm that affects the process has occurred. In the 3200, this is set if any of the 4
alarms are set, or if Sensor Break, Span Error, or Loop break is set.
ALARM, MACHINE
BIT#
2
DESCRIPTION:
This bit indicates that an alarm that affects the machine has occurred. Always set to 0 for 3200.
FAULT, SENSOR
BIT#
2
DESCRIPTION:
This bit indicates a sensor error has been detected. Either sensor break or span error for 3200.
TEMPERATURE, TO PROCESS
POLL:
20 70
SELECT:
N/A
FORMAT:
Numeric
UNITS:
ºF
DESCRIPTION:
Returns the “To Process” Temperature