3200 Series
26 ACS 3216 Operators Manual
SETPOINT PROCESS TEMPERATURE
POLL:
20 30
SELECT:
20 31
FORMAT:
Numeric
UNITS:
ºF
DESCRIPTION:
Temperature at which the process is to be maintained.
ALARM, HIGH TEMPERATURE DEVIATION
POLL:
20 32
SELECT:
20 33
FORMAT:
Numeric
UNITS:
ºF
DESCRIPTION:
This Value in conjunction with the process setpoint determines at what temperature the high alarm will occur.
It must always be positive. NB: in the 3200 this setpoint relates to the first
configured alarm in the instrument
and is therefore not necessarily a high temperature alarm.
ALARM, HIGH TEMPERATURE DEVIATION
POLL:
20 34
SELECT:
20 35
FORMAT:
Numeric
UNITS:
ºF
DESCRIPTION:
This Value in conjunction with the process setpoint determines at what temperature the low alarm will occur.
It must always be positive. NB: in the 3200 this setpoint relates to the second
configured alarm in the
instrument and is therefore not necessarily a low temperature alarm.