7. TIMER OPERATION
A timer can be configured to operate in three different modes. These can be
selected in Level 2.
1. Dwell timer
2. Delayed switch on timer
3. Soft start timer
There are four operating states, all of which are available in Level 1:
Run may be initiated by pressing
and together.
Reset (of End State) when timer has timed out, may be initiated by pressing
and (Ack),
Reset, during timing, may be initiated by pressing and holding
and
(Note pressing Ack at this point does not reset the timer. The reason for this
is that if the display is on any view other than the HOME display then
pressing these two buttons will jump to HOME).
Hold may be initiated by pressing
and To run the timer from
hold, press quickly
and again
The above states may also be set by the following methods:-
• Edge trigger a suitably configured digital input
• Power cycle the controller
• Digital communications command
End cannot be set - it occurs automatically when the timer has counted
down to zero
Switching from Hold to Run through the front panel buttons is not allowable
if the Hold status is forced by a logic input or through Digital
Communications.
Timer operation is indicated by a beacon labelled RUN:
Timer Status RUN beacon
Reset Off
Run On
Hold Flashing
End Off
Logic outputs The timer may be configured to operate an output when it is
running or during the end state
Note:-
• Power up - the ‘run’ state is selected if a Soft Start or Delay
timer is configured or the ‘Reset’ state is selected if a Dwell timer
is configured.
• Auto/Manual is only available when the timer is in Reset
• Ramp Rate – it is recommended that ramp rate is used only with
a Dwell type timer
• Quick access to the timer operating parameters is available in
Level 2 by pressing
. Repeat pressing of this button shows
Timer Status, Dwell, Working Output, SP1, SP2, etc
7.1. Dwell Timer
A dwell timer (TI.CFG = DWELL) is used to control a process at a fixed
temperature for a defined period. The action which occurs at the end of the
timed period depends on the configuration of the END.T parameter.
Notes:
1. If THRES = 2
o
(for example) timer will show TIMER RUNNING with
the RUN beacon on but will not start counting down until the
temperature is, first, within 2
o
of SP. Then the threshold is ignored.
2. The DWELL period can be reduced or increased when the timer is
running. If it is reduced to meet the Time Elapsed the timer will
change to the End state.
3. A-M can only be selected when in reset
4. If the timer is re-configured to a different type or the End Type is re-
configured (a dwell, for example), it may be necessary to reselect Auto
mode
7.1.1. Simple Programmer
A four segment programmer is achieved using a dwell type timer with the set
point rate limit and threshold parameters set.
7.2. Delayed Switch On timer
The timer is used to switch on the output power after a set time.
When the timer status = run, the control output is off
When the timer status = reset, the control output is controlling at SP1
7.3. Soft Start Timer
The timer is used to start a process at reduced power and/or reduced
setpoint. Timing starts at power up or when ‘Run’ is selected.
When the Timer Status = Run, the controller power is limited by the soft
start power limit parameter. The Soft Start setpoint is a threshold which,
when exceeded, sets the timer to end. If the temperature is already above
this threshold when the timer is set to run, the timer will time out
immediately.
When the timer status = reset, the controller is controlling at SP1
TIMER END
OFF
End State end. t =
OFF SP2 dwel
SP2
Temp
SP1
Time
THRES
= + n
RUN Digital O/P = t.run
END Digital O/P = t.End
RESET
Digital Input
OF
TIMER RUNNING
OFF
Scrolling
message
Counting
down
Temperature
RUN Digital O/P = t.run
Reset Run
RESET
Digital
input
SP1 (70)
Time
TIMER RUNNING TIMER END
Scrolling
Message
END Digital O/P = t.End
TIMER
RUNNING
TIMER
END
Timer soft start power limit
SS.PW R (40%)
Run
RESET
Digital input
Temp
Setpoint (70
o
C)
Time
Time
Output power High limit
Soft start setpoint
SS.SP (50
o
C)
RUN Digital O/P = t.run
END Di
ital O/P = t.End
Reset
Scrolling
Message
Servo
to PV
start
THRES
= +
n
RESET
Digital
input
RUN Digital O/P = t.run
END Digital O/P = t.End
Temp
SP1
70
o
C
Time
SP2
20
o
C
Ramp to
SP1 at
SP.RAT
DWELL
Ramp to
SP2 at
SP.RAT
Counting down
TIMER RUNNING
TIMER
END
Scrolling
message